Model 41001Series Semi-Recessed 405Catalog 405-10 W Cabinet
41001 Cato Chief Semi-Recessed 10 lb Plastic Fire Extinguisher Cabinet, ADA Projection
Shipping and tax calculated at checkout.
- Fits JL Industries Cosmic up to 10 lb, Amerex B456 10 lb, Strike First 10 lb
- Wall opening 10-1/2" W x 25" H x 4" D (wall opening)
- One year Activar CPG warranty
Description
The Cato 41001, still widely called the 405-10, is the Chief Semi-Recessed plastic fire extinguisher cabinet. It sets into the wall and leaves only a 2-7/8 inch trim projection, which is inside the 4 inch limit the ADA standards put on objects protruding into a circulation path. That is the reason to choose it: a surface mount cabinet in a corridor often is not compliant, and this one is.
- Cato catalog numbers: 41001 plain, 41001L with the cylinder lock
- Prior catalog name: Classic Semi-Recess 405-10
- Trim projection: 2-7/8" rounded edge
- Tub inside dimensions: 8-1/2" W x 23-1/4" H x 5-5/8" D
- Trim outside dimensions: 13-3/8" W x 27-5/8" H, 2-7/8" projection
- Wall opening required: 10-1/2" W x 25" H x 4" D
- Door: 8-5/8" W x 23" H, hinged, with a viewable acrylic window and pull handle
- Cabinet weight: 5 lb
- Tub and trim material: injection moulded polypropylene in .15 thickness, white only
- Window: .080 acrylic, clear only
- Hardware: stainless steel hinge, glass clip, handle and roller catch
- Decals: red vertical FIRE EXTINGUISHER decal and a black vertical IN CASE OF EMERGENCY decal, both included
- Options: cylinder lock with flexible cam (41001L), fire extinguisher rust prevention tray (Cato 10300)
- Mounting: semi-recessed
Extinguishers this cabinet holds:
- JL Industries, listed by Cato on the submittal: Cosmic 2.5-10, Galaxy 2.5-10, Mercury 2.5-5, Sentinel 5.
- Strike First, by cylinder diameter and height: SF-ABC110ST 2-1/2 lb ABC; SF-ABC310 5 lb ABC; SF-ABC680 10 lb ABC; SF-5CO2 5 lb CO2.
- Amerex, by cylinder diameter and height: B417T and B417TS 2-1/2 lb ABC; B402 and B500 5 lb ABC; B424 5 lb ABC; B443 6 lb ABC; B461 6 lb ABC; B456 10 lb ABC; B441 10 lb ABC; 720 10 lb ABC high flow.
Cato's own figures are the tub inside dimensions above. The Strike First and Amerex models listed are the ones whose published cylinder diameter clears the tub width and depth and whose overall height clears the tub height; the published width of a portable extinguisher includes its hose and handle, which sit beside the cylinder. Units marked tight fit have less than 1/4 inch to spare, so measure the extinguisher you actually own before ordering.
Mounting height: Activar's method is to take the wall opening height and work back from the 48 inch handle limit. For this cabinet's 25 inch wall opening with a centred pull, that is 48" - (25" / 2) = 35-1/2" above the finished floor to the bottom of the opening.
Activar warrants fire protection products other than extinguishers, including cabinets and alarm covers, free from defects in materials and workmanship for one year from date of shipment. Manufacturer warranty terms and conditions apply in all cases.
Specs
| Cabinet | |
|---|---|
| Series | Cato Chief Semi-Recessed |
| Model | 405-10 |
| Catalog numbers | 41001 plain, 41001L with cylinder lock |
| Extinguisher class | 10 lb |
| Mounting | Semi-recessed |
| Colour | White only |
| Trim style | 2-7/8" rounded edge |
| Dimensions and weight | |
|---|---|
| Trim projection | 2-7/8" |
| Tub inside dimensions | 8-1/2" W x 23-1/4" H x 5-5/8" D |
| Trim outside dimensions | 13-3/8" W x 27-5/8" H |
| Wall opening required | 10-1/2" W x 25" H x 4" D |
| Door size | 8-5/8" W x 23" H |
| Cabinet weight | 5 lb |
| Materials | |
|---|---|
| Tub and trim material | Injection moulded polypropylene, .15 thickness |
| Window material | .080 acrylic, clear |
| Hardware | Stainless steel hinge, glass clip, handle and roller catch |
| Lock option | Cylinder lock with flexible cam, 41001L |
| Decals | Red vertical FIRE EXTINGUISHER and black vertical IN CASE OF EMERGENCY, included |
| Standards | |
|---|---|
| ADA projection | 2-7/8" trim projection, inside the 4" maximum for objects protruding into a circulation path between 27" and 80" AFF |
| Mounting height | Bottom of a 25" wall opening at 35-1/2" AFF for a centred pull |
| Warranty | One year from date of shipment |
| Origin | Made in the USA |
Documents
- Chief Semi-Recessed submittalDimension table, wall opening and replacement parts for the Chief Semi-Recessed cabinet
- Cabinet installation instructions 14I-120Surface and semi-recessed cabinet installation
- ADA mounting height and projectionCato technical article on cabinet mounting height and the 4 inch projection rule
- How to select a cabinet for a portable fire extinguisherActivar's cabinet sizing rule
- Fire protection catalogFull Cato and JL Industries fire protection catalog
- Fire protection warranty certificateOne year on fire protection cabinets and equipment
Buyers ask
Is the Cato 41001 ADA compliant?
Its 2-7/8 inch trim projection is inside the 4 inch maximum the ADA standards allow for an object protruding into a circulation path between 27 and 80 inches above the floor. You still have to mount it so the handle sits no higher than 48 inches above the finished floor.
What size wall opening does the 41001 need?
10-1/2" wide x 25" high x 4" deep.
What is the difference between 41001 and 41001L?
The 41001L adds a cylinder lock with a flexible cam. The cabinet is otherwise identical.
Is the 41001 the same as the 405-10?
Yes. 405-10 is the older catalog name for the same cabinet; Activar's current marketing name is Chief Semi-Recessed.
What colour does it come in?
White only. Unlike the surface mount Chief, the semi-recessed cabinet is moulded in polypropylene and is not offered in red.
How high should I mount it?
Activar takes the 48" handle limit and subtracts half the wall opening height. For this cabinet: 48" - (25" / 2) = 35-1/2" above the finished floor to the bottom of the opening.
Nearby models
41001L
Classic Semi-Recessed 405-10 Fire Extinguisher Cabinet with Lock, White
- Size
- 10 lb
- Tub I.D.
- 8-1/2" W x 23-1/4" H x 5-5/8" D
- Ship wt
- 5 lb
10501-H
Chief 5 lb Plastic Fire Extinguisher Cabinet, White, Break panel with hammer
- Size
- 5 lb
- Tub I.D.
- 6" W x 16-3/4" H x 5-3/8" D
- Ship wt
- 3.5 lb
10501-B
Chief 5 lb Plastic Fire Extinguisher Cabinet, White, Break panel with stainless break bar
- Size
- 5 lb
- Tub I.D.
- 6" W x 16-3/4" H x 5-3/8" D
- Ship wt
- 3.5 lb
11001-H
Chief 10 lb Plastic Fire Extinguisher Cabinet, White, Break panel with hammer
- Size
- 10 lb
- Tub I.D.
- 6-3/4" W x 20-1/2" H x 6" D
- Ship wt
- 4.5 lb
Read next
- Guide
Which Cato Cabinet Fits My Fire Extinguisher
Match a Strike First, Amerex or JL Industries extinguisher to the right Cato tub using the published tub I.D. dimensions from Cato's submittals.
- Guide
Fire Extinguisher Cabinet Mounting Height and ADA Projection
How high to mount a fire extinguisher cabinet, the 4 in. ADA protruding-objects limit, and the formula Cato publishes for calculating wall opening height.
- Guide
Plastic vs Steel Fire Extinguisher Cabinets
What a molded polystyrene Cato cabinet does that a steel box cannot: no dents, no rust, lighter freight, and a non-magnetic option for MRI rooms.